The Ultra1000 Series is a 24 VDC powered gas detector to monitor combustible Hydrocarbon vapors in air. The complete sensor consists of a stainless steel sensor head assembly and an interface module enclosed in a flame proof instrument enclosure.
Interface module generates a 4-20mA signal proportional to 0 to 100% of the detection range. Digital display and two (2) fully programmable alarm relays for Low and high gas alarm are also provided on the interface module. A half-duplex RS-485 port for MODBUS RTU communication to user PLC or control system.
The detectors feature a simple non-intrusive automated calibration without any manual adjustments. Analog signal and alarm relays are inhibited during calibra- tion mode to avoid any unnecessary or false alarms.
Sensor Type
Continuous diffusion / absorption
Non-dispersive Infrared Optical (NDIR)
Measuring Range
Repeatability
Zero Drift
Explosion Proof Enclosure
ATEX: | II 2G Ex d IIC T6 |
CSA: |
Class I, Div 1 & 2, Groups B, C & D |
Operating Temperature Range
Height: | 7.4 inches ( 188 mm) |
Width: | 6.2 inches (159 mm) |
Depth: | 4.9 inches (125 mm) |
Ingress Protection
NEMA4X, IP66
Display and Indicators
2 line by 8 character LED display with backlights for gas reading, Alarms and Fault Condition
Power Input
< 2 Watts
Typical Sensor Life
Alarm Relays
Programmable Low and High Alarms, Fault Alarm
SPDT Form “C” Relays
2 A @ 250 VAC or 30 VDC
Calibration
Fault: | 0 mA |
Calibrate Mode: | 2 mA |
Over Range: | > 21 mA |
Serial Communication
MODBUS RTU Protocol
Transient over voltage suppressor
Reverse Polarity protection
EMI / RFI Immunity
Three wire shielded cable for power and analog signal.
Max of 300 Ω load for analog output
Dust or Splash guard, Flow Adapter with tube fittings, Sensor Duct Mount Kit, Pole Mount brackets.
3/4" NPT Female
Adapter available for 1/2" NPT or M20
Two year Electronics
One year Sensor head assembly
© 2020 – 2025 Pem-Tech, Inc. 12144 Dairy Ashford, Building 2, Sugar Land, TX 77478 Toll Free: 800-379-3894Phone: 281-494-2079Fax: 281-494-2167